Rated Voltage |
kV |
12 |
24 |
Main busbar rated current |
A |
630 |
630 |
Main loop, earthing loop rated short time withstand current |
kA/s |
20/3 |
20/3 |
Main loop, earthing loop rated peak withstand current |
kA |
50 |
50 |
Main loop, earthing loop rated short circuit making current |
kA |
50 |
50 |
Mechanical life |
Times |
2000 |
2000 |
Mechanical life |
Times |
2000 |
2000 |
1min P.F. Withstand(virtral value),phase to phase,earth/across open contacts |
kV |
38 |
50 |
Lightning impulse withstand voltage(peak),phase to phase,earth/across open contacts |
kV |
75/95 |
125 |
Secondary loop 1min P.F. Withstand |
kV |
2 |
2 |
Protection degree |
– |
IP3X |
IP3X |